TM-9-2920-257-30&P Maintenance and Parts Manual for 200 Amp M113 Generator Download

Page 18 of 111

TM 9-2920-257-30&P Table 2-1. Generator Troubleshooting - Continued MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION Figure 2-9. Shorted Printed Circuit Panel Step 11. Check for shorted or high Assembly Capacitor Check. leakage capacitors between battery positive and field positive according to figure 2-9. NOTE Ohmmeter may deflect to low resistance reading momentarily and then climb to a high resistance reading. This is normal when checking capacitors. The final ohmmeter reading is to be used in this test. If ohmmeter reading is less than 100,000 ohms, capacitors are shorted. Replace printed circuit panel assembly in accordance with paragraph 3-3 and go to step 13. 2-11