TM-9-2920-257-30&P Maintenance and Parts Manual for 200 Amp M113 Generator Download

Page 14 of 111

TM 9-2920-257-30&P Table 2-1. Generator Troubleshooting - continued MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION Figure 2-5. Open Negative Rectifier Test. Step 7. Check for open negative rectifiers. Connect ohntmeter to each of the three negative rectifier leads in accordance with figure 2-5. If the ohmmeter reading is more than 100 ohms, replace drive end housing assembly in accordance with paragraph 3-3, and go to step 8. 2-7