TM 9-2920-257-30&P Table 2-1. Generator Troubleshooting - Continued MALFUNCTION TEST OR INSPECTION CORRECTIVE ACTION Figure 2-3. Open Positive Rectifier Test. Step 5. Check for open positive rectifiers. Connect ohmmeter to each of the three positive rectifier leads in accordance with figure 2-3. If the ohmmeter reading is more than 100 ohms, replace drive end housing assembly in accordance with paragraph 3-3, and go to step 8. 2-5