TM 9-2350-261-10 PREVENTIVE MAINTENANCE CHECKS AND SERVICES — Continued 0075 00 ITEM NO. INTERVAL MAN- HOUR ITEM TO BE CHECKED OR SERVICED CREWMEMBER PROCEDURE EQUIPMENT NOT READY/ AVAILABLE IF: 10 Before Fixed Fire Extinguisher DRIVER WARNING A fire can break out at any time. Personnel could be killed or injured. Equipment could be damaged. Make sure both fire extinguishers are ready to use before you operate carrier. C A U T I O N Inspect cylinder/bottle data to ensure the latest hydrostatic test was performed within the past 5 years. Any bottle/cylinder beyond the test time limit shall be declared unserviceable and replaced. a. Inspect fire extinguisher cylinder data plate to ensure that a hydrostatic test has been performed within the past 5 years. Faulty extinguishers or those beyond the test time limit (5 years) shall be declared unserviceable and replaced. Cylinders/ bottles are overdue for a hydrostatic test. b. Check fixed extinguisher control seal. Extinguisher missing. c. Make sure seal or lockwire is not broken. Report broken seal to unit maintenance. Seal or lockwire missing or broken. d. Check for full charge. 0075 00-22