TM-9-2920-225-34 Technical Manual for Generators AMA5102UT 3002AC and 3002AD Download

Page 84 of 262

TM 9-2920-225-34 FRAME 2 1. 2. 3. GO Check that stator windings (1) has no loose or frayed insulation. Check that connector (2) has no loose or damaged pins. Check that stator (3) is not grounded by using a multimeter and touching one test probe to housing and the other test probe to each pin or connector (2). Each connection must indicate an open circuit. If circuit is closed, generator is nonrepairable. TO FRAME 3 TA103569 2-68