TM-9-2320-366-20-3 MTV Unit Maintenance Manual M1083 Series - Volume 3 Download

Page 359 of 1396

Change 2 2-2285 TM 9-2320-366-20-3 CONTINUITY TEST (1) Remove circuit breaker CB1 from Power Distribution Panel (PD2). (2) Set multimeter to ohms. (3) Connect positive (+) probe of multimeter to one terminal of circuit breaker CB1. (4) Connect negative (-) probe of multimeter to other terminal of circuit breaker CB1 and note reading on multimeter. (5) If continuity is not present, replace circuit breaker CB1 (para 20-80). (6) Install circuit breaker CB1 in Power Distribution Panel (PD2).