NO TM 9-2320-365-20-2 2-1206 Change 1 e110. M1079 110 VAC OUTLET J231 DOES NOT OPERATE (CONT) 7. KNOWN INFO POSSIBLE PROBLEMS TEST OPTIONS Continuity Test or STE/ICE-R Test #91 REASON FOR QUESTION Replace relay K35 (para 16-62). 110 VAC outlets J230, J232, J233, and J235 OK. 110 VAC outlet J234 does not operate. Circuit breaker CB7 OK. Wire 701B OK. Faulty wire 702B. Faulty relay K35. Is continuity present on wire 702B from K35 relay base terminal 5 to 110 VAC receptacle J231 supply pole? If continuity is not present, wire 702B is faulty. If continuity is present, relay K35 is faulty. YES Repair or replace wire 702B (para 2-40).