TM-9-2320-365-20-2 LMTV Unit Maintenance Manual M1078 Series - Volume 2 Download
Page 1087 of 1432
Change 2 2-1997  TM 9-2320-365-20-2  (1) Remove circuit breaker CB5 from Power  Distribution Panel (PD1).  (2) Set multimeter to ohms.  (3) Connect positive (+) probe of multimeter to  one terminal of circuit breaker CB5.  (4) Connect negative (-) probe of multimeter to  other probe of circuit breaker CB5 and note  reading on multimeter.  (5) If continuity is not present, replace circuit  breaker CB5 (para 20-87).  (6) If continuity is present, perform Special  Purpose Kit Troubleshooting task u1. No  Power to Digitization Rack.  Perform steps (7) through (10), if  continuity is present through circuit  breaker CB5.  (7) Install circuit breaker CB5 in Power  Distribution Panel (PD1)  (8) Position electrical distribution block cover  on power distribution shelf.  (9) Tighten wing nut on electrical distribution  block cover.  (10) Install wing screw on power distribution  shelf.  CONTINUITY TEST  NOTE